RADIK HYGIENE VK

Steel panel radiator for rooms with high demands on hygiene and cleanness, with flat front panel and right bottom connection

Steel panel radiator for rooms with high demands on hygiene and cleanness, with flat front panel and right bottom connection

RADIK HYGIENE VK is a panel radiator in VENTIL KOMPAKT version which enables right bottom connection to the pressurized heating system.

It is suitable for installation and operation in rooms with high demands on hygiene and cleanness. All types are without convector fins; they have a flat front panel and the seam welds are covered with a special flat strip. The type 20S has got a bigger spacing between the panels (radiator depth B = 102 mm) as compared to the standard spacing of type 20 (B = 66 mm).

There are two upper and two lower hangers welded at the back side of the radiator. Radiators in length 1 800 mm and more have six hangers. An air-vent and blanking plugs are delivered as standard. We recommend using the drill-in brackets (type 18/120 – see the KORAMONT catalogue) which enable to mount the radiator in a distance of up to 65 mm from the wall.

Notice: If the requested distance between the radiator and the wall should be 65 ÷ 80 mm, the same type of brackets can be used on condition that the lower hangers are fixed with brackets (not with supporting pieces only). In such a case the additional brackets must be ordered extra.

Technical Data

Height (H) 503, 603 mm
Length (L) 404, 504, 604, 704, 804, 904, 1004, 1104, 1204, 1404, 1604, 1804, 2004 mm
Depth (B)
- Type 10 HYGIENE VK 49 mm
- Type 20S HYGIENE VK 102 mm
- Type 30 HYGIENE VK 157 mm
Connecting pitch 50 mm
Connecting thread 6 × G½ inside
Highest allowed working pressure 10 bar
Highest allowed working temperature (°C) 110 °C
Radiator connection right bottom
Pressure Loss

In case of two-pipe heating system it is necessary to calculate the correct level of valve presetting and specify this in the project documentation to ensure a proper function of the heating system. This must be kept by the installer during installation of the heating system.

In case of one-pipe heating system it is necessary to set the valve at level 6. For adjusting the required mass flow in the radiator we recommend to use the compact connecting fitting with a fixed or adjustable flow volume of water in the radiator.


Heat output [W]

Heat output calculated to ∆T= 50; (t1/t2/ti = for 75/65/20 °C)

Type 10 HYGIENE VK Type 20S HYGIENE VK Type 30 HYGIENE VK
Height [mm] Height [mm] Height [mm]
Length [mm] 503 603 503 603 503 603
404 172 198 323 376 461 533
504 216 248 404 471 577 667
604 259 298 485 565 692 800
704 302 347 566 659 807 933
804 345 397 646 753 922 1066
904 388 446 727 847 1038 1200
1004 431 496 808 941 1153 1333
1104 474 546 889 1035 1268 1466
1204 517 595 970 1129 1384 1600
1404 603 694 1131 1317 1614 1866
1604 690 794 1293 1506 1845 2133
1804 776 893 1454 1694 2075 2399
2004 862 992 1616 1882 2306 2666